Dayu Electronics Ultrasonic Level Meter Buzzer Alarm Wiring Instructions
Dayu Electronics ultrasonic level meter with relay output can be connected to a buzzer for level alarm. When wiring, it is important to confirm the supply voltage is consistent and correctly connect to the relay output terminals.
Buzzer supply voltage must match the level meter
The rated voltage of the buzzer should match the level meter supply voltage. If the level meter uses 24 VDC power, the buzzer should also be a 24 VDC type; if the level meter uses 220 VAC power, the buzzer should be a 220 VAC type. Voltage mismatch may cause the buzzer not to sound or to burn out.


Connect the buzzer directly to the level meter relay output
The two buzzer wires can be connected directly to the relay output terminals of the level meter. The relay is normally open. When the liquid level reaches the preset alarm level, the relay closes, voltage forms a loop through the buzzer cable, and the buzzer sounds. During wiring, pay attention to the positive/negative or live/neutral correspondence to avoid reverse connection.

Confirm that the relay contact capacity meets the buzzer load
Before wiring, confirm that the contact capacity of the level meter relay is greater than the buzzer operating current. If the buzzer power is relatively high, it is recommended to use the level meter relay to drive an intermediate relay, and then use the intermediate relay to control the buzzer to protect the internal contacts of the level meter.

It is recommended to have the Dayu Electronics technical team assist in confirming the wiring plan
Different level meter models may have different relay types, contact capacities, and output modes. It is recommended to provide the specific level meter model, supply voltage, and buzzer specifications so Dayu Electronics can assist in confirming the wiring method and whether an intermediate relay is needed.